Gard highlights mass flow meter 'discrepancies'


P&I club issues recommendations to ensure bunker barge operator compliance.



Source: Gard

Protection and indemnity (P&I) insurer Gard aims to address in this article the issues faced by members when taking bunkers in Singapore following the mandatory implementation of mass flow meters (MFM) for bunker suppliers. The introduction of mandatory use of MFMs was intended to address frequent quantity disputes arising between the bunker barge and the receiving vessel, although issues remain.

Causes of the discrepancies

There have been two main causes of the discrepancies when using the mass flow meter;

- Operational practices by the bunker barge operators, and

- Limitations of the equipment itself.

Operational practices

Gard has received reports indicating that some bunker barges were found to syphon fuel back to their tanks via pipe connections between the flow meter and the outlet flange going to the ship manifold. In such circumstances the MFM reading will be higher than the amount actually received by the ship's bunker tanks.

The Maritime Port Authority of Singapore is currently investigating these issues and has suspended several barges from operations until completion of the investigation. It is worth noting that an MPA-certified bunker barge should have all connections between the flow meter and the shipside blanked off and sealed as part of the certification.

Limitations of the MFMs

Some vessels have recently reported quantity difference exceeding their past experience. Some bunker surveyors have studies the discrepancy between the MFM readings and the vessel received figures for a duration of time. Out of 24 cases of discrepancies over the duration, the maximum discrepancy was 57.24 MT and minimum 6.79 MT. The average discrepancy, in the disputed cases, was approximately 19 MT.

These discrepancies can be due to:

- Errors in the tank calibration tables for the receiving vessel.

- Errors in the MFM's measurement of the flow rate.

Any errors in the tank calibration of the vessel would be consistent with or without the MFM. To identify this issue a vessel experience factor (VEF) from her previous bunkering operations should be taken into account.

Errors in the MFM reading can also account for such discrepancies. All MFMs have a maximum and minimum flow rate, commonly known as 'Qmax' and 'Qmin' respectively. These limits define the operational accuracy within which the system is qualified to operate. In other words, if the flow rate of the liquid is outside these limits, the calibration of the equipment may not be accurate. It is seldom that the flow rate exceeds the Qmax, as it is usually about 1,000 t/h (forward flow). However, during stripping of the bunker barge's tanks, the flow rate can frequently fall below the Qmin. The longer the duration of the stripping, the more likelihood of a discrepancy between the MFM and the ship's received figures.

Additionally, MFM parameters such as Damping, Drive Gain, Low Flow Cut Off Value & Air Index can affect the accuracy of measurement if they exceed the manufacturers' recommended limits during the bunkering operation.

While stripping of the bunker tanks is allowed under the TR48 (Technical Reference For Bunker Mass Flow Metering), it has been noted that prolonged stripping operations causes frequent fluctuations in the flow rate with several instances of the flow rate falling below the Qmin. It has also been observed that some bunker barges conduct stripping operations in the middle of bunkering which is not permitted under TR48 and can lead to measurement uncertainty.

Recommendations

To ensure that bunker barge operators comply with all the necessary requirements, Gard recommends the following;

1. Compare the certificate of the MFM with the actual equipment fitted on the barge (comparing the serial number) to verify that the certificate is for the equipment actually fitted.

2. Seal checks: there are a number of seals, up to 20 in some cases, fitted on the MFM and other piping on the barge. These seals have to be checked and verified before every delivery.

3. The bunker surveyors should inspect the barge piping, especially around the manifold areas for any drain lines, fittings or stub pieces from where bunker oil may be tapped back into the barge tanks. If any such fittings are found, the surveyors are instructed to seal any valves leading to such fittings and report the vessel's chief engineer to the Maritime Port Authority of Singapore. The surveyor should also ensure that the Meter Totalizer Log is available for inspection as required under TR48.

4. Meter Zero should be the last thing that is done before commencing the bunker delivery and must always be done AFTER the hose has been fitted to the ship's manifold.

5. Where the bunker surveyor has been engaged, the survey report should indicate an evaluation of the meter profile in order to ensure that the basic MFM profile parameters (Qmin, Damping, Drive Gain, Low Flow Cut Off Value & Air Index) are within operating limits.

6. If there is significant discrepancy between the vessel received figures and the MFM figures after having physically verified all the above points, the following actions are recommended:

7. Repeat steps 2 and 3 as stated above.

8. Inform the MPA following the guidelines on 'Mass Flow Meter Dispute Management'

9. Engage an MFM advisor to study the meter profile in detail. This will involve the MFM profile ASCII files, Transmitter Configuration Report etc. The surveyor should also be asked to provide an independent opinion on the validity of the delivered quantity.

In addition to the physical checks, members and clients could consider incorporating protective clauses in their bunker purchase contracts. The protective clauses could include the provision of the need to physically check the bunker quantities on the delivery barge before and after bunkering.


Chang Ping Yuan vessel. Cosco Shipping names 88,000-cbm VLGC Chang Ping Yuan with dual-fuel LPG propulsion  

Owner claims 20% CO₂ reduction and Panama Canal compatibility across both lock systems.

World Fuel logo. World Fuel seeks senior marine fuels sales executive in London  

Position requires minimum of 10 years' experience in marine fuels, marine energy, or shipping.

Amogy and LOTTE Fine Chemical MoU signing. Amogy and LOTTE Fine Chemical sign MoU to advance ammonia solutions in South Korea  

Partnership structured around ammonia bunkering, hydrogen refuelling infrastructure, and distributed ammonia-to-power generation.

WinGD X72DF-ME engine render. WinGD wins order for dual-fuel alcohol engines for Polaris Shipping Newcastlemax fleet  

Four-engine order giving shipowner methanol and ethanol fuel flexibility.

Trelleborg Marine and Infrastructure logo. Trelleborg and Simwave launch LNG transfer equipment training programme at Gastech 2026  

New e-learning programme aims to close crew competency gaps as LNG bunkering grows and alternative fuels enter service.

Toho Emerald vessel. K Line names dual-fuel LNG carrier Toho Emerald at Samsung Heavy Industries yard  

174,000-cbm vessel, built for a joint venture with Toho Gas, is due for delivery next month.

Fujin Sailor vessel. MOL names world’s first LNG carrier fitted with wind-assisted propulsion for Chevron charter  

Fujin Sailor is also the first vessel of any type to carry two Wind Challenger units.

Steve Esau, Sea-LNG. SEA-LNG urges EU to protect mass-balance pathway for liquefied biomethane  

Industry coalition warns regulatory missteps could undermine LBM's rapid growth in maritime.

Luxomar delivery ceremony. ESL Shipping completes Green Coaster fleet with delivery of twelfth vessel Luxomar  

Baltic dry bulk carrier has finalised a twelve-vessel plug-in hybrid coaster programme built in India.

Hybrid ro-ro vessel render. Compagnie Maritime Nantaise orders hybrid ro-ro vessel for European space cargo runs  

French shipping company commissions wind-assisted vessel with biofuel capability to serve growing European space industry.


↑  Back to Top